NOTE: Two consecutive Load instructions will place the value of the first load instruction onto the
accumulator stack.
In the following example, when C0 is on, the binary pattern of C10–C16 (7 bits) will be
loaded into the accumulator using the Load Formatted instruction. The lower 7 bits of the
accumulator are output to Y0–Y6 using the Out Formatted instruction.
bbb
K
LDF
A aaa
Operand Data Type
DL06 Range
A
aaa
bbb
Inputs
X
0–777
––
Outputs
Y
0–777
––
Control Relays
C
0–1777
––
Stage Bits
S
0–1777
––
Timer Bits
T
0–377
––
Counter Bits
CT
0–177
––
Special Relays
SP
0–777
––
Constant
K
––
1–32
Discrete Bit Flags
Description
SP70
On anytime the value in the accumulator is negative.
SP76
On when any instruction loads a value of zero into the accumulator.
0
A
7
H
ENT
Handheld Programmer Keystrokes
LDF
C10
K7
C0
Load the status of 7
consecutive bits (C10–C16)
into the accumulator
OUTF
Y0
K7
Copy the value from the
specified number of bits in
the accumulator to Y0 – Y6
K7
C10
Location Constant
0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Acc.
K7
Y0
Location
Constant
C16 C15 C14 C13 C12 C11 C10
OFF
ON
ON
ON
OFF
OFF
OFF
Y6 Y5 Y4 Y3 Y2 Y1 Y0
OFF
ON
ON
ON
OFF
OFF
OFF
The unused accumulator bits are set to zero
Direct SOFT32
STR
$
SHFT
ENT
2
C
0
A
SHFT
ANDST
L
3
D
5
F
SHFT
2
C
1
B
0
A
7
H
ENT
OUT
GX
SHFT
5
F
DS
Used
HPP Used
Direct
SOFT
Load Formatted (LDF)
The Load Formatted instruction loads 1–32 consecutive bits
from discrete memory locations into the accumulator. The
instruction requires a starting location (Aaaa) and the number
of bits (Kbbb) to be loaded. Unused accumulator bit locations
are set to zero.