DL06 Micro PLC User Manual, 3rd Edition, Rev. E
Chapter 2: Installation, Wiring, and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
2-6
Terminal Block Removal
The DL06 terminals are divided into two groups. Each group has its own terminal block. The
outputs and power wiring are on one block, and the input wiring is on the other. In some
instances, it may be desirable to remove the terminal block for easy wiring. The terminal block is
designed for easy removal with just a small screwdriver. The drawing below shows the procedure
for removing one of the terminal blocks.
1. Loosen the retention screws on each end of the connector block.
2. From the center of the connector block, pry upward with the screwdriver until the
connector is loose.
The terminal blocks on DL06 PLCs have regular (m3 size) screw terminals, which will
accept either standard blade-type or #1 Philips screwdriver tips. Use No. 16 to 22 AWG
solid/stranded wire. Be careful not to over-tighten; maximum torque is 0.882 to 1.020 N·m
(7.806 to 9.028 in·lbs).
Spare terminal blocks are available in an accessory kit. Please refer to part number
D0-ACC-2. You can find this and other accessories on our web site.