Wiring Guidelines
Connect the power input wiring for the DL06. Observe all precautions stated earlier in this
manual. When the wiring is complete, close the connector covers. Do not apply power at
this time.
WARNING: Once the power wiring is connected, secure the terminal block cover in the closed
position. There is a risk of electrical shock if you accidentally touch the connection terminals or
power wiring when the cover is open.
External Power Source
The power source must be capable of suppling voltage and current complying with
individual Micro PLC specifications, according to the following specifications:
NOTE: The rating between all internal circuits is BASIC INSULATION ONLY.
NOTE: Recommended wire size for field devices is 16–22 AWG solid/stranded. Tighten terminal
screws to 7.81 lb·in (0.882 N·m) to 9.03 lb-in (1.02 N·m).
LOGIC
Koyo
06
C0
C4
C2
X1
X3
X4
X6
X11 X13 X14
X16
X21 X23 N.C.
C1
C3
X2
X5
X7
X10 X12
X15 X17 X20 X22
X0
N.C.
AC(N) 24V
0V
N.C.
C1
C3
Y0
Y15
Y12
Y10
Y17
Y7
Y5
Y2
C0
C2
Y16
Y14
Y13
Y11
Y6
Y4
Y3
Y1
LG
G
AC(L)
D0-06AA
40VA
50-60Hz
PWR: 100-240V
OUTPUT: 17-240V
50 - 60Hz 0.5A
Y
X
7 - 15mA
INPUT: 90 - 120V
0
1
2
3
4
5
6
7
10 11 12 13 14 15 16
17 20 21 22
23
fuse
LOGIC
Koyo
06
DC
Supply
C0
C4
C2
X1
X3
X4
X6
X11 X13 X14
X16
X21 X23 N.C.
C1
C3
X2
X5
X7
X10 X12
X15 X17 X20 X22
X0
N.C.
C1
C3
Y0
Y15
Y12
Y10
Y17
Y7
Y5
Y2
C0
C2
Y16
Y14
Y13
Y11
Y6
Y4
Y3
Y1
+V
+
-
LG
N.C.
N.C.
G
OUTPUT: Sinking Output 6 - 27V
1.0A
INPUT: 12 - 24V
3 - 15mA
Y
X
PWR: 12-24
20W
D0-06DD1-D
0
1
2
3
4
5
6
7
10 11 12 13 14 15 16
17 20 21 22
23
+
-
12 - 24 VDC
110/220 VAC Power Input
12/24 VDC Power Input
Power Source Specifications
Item
DL06 AC Powered Units
DL06 DC Powered Units
Input Voltage Range
110/220 VAC (100–240 VAC/50-60 Hz)
12–24 VDC (10.8–26.4 VDC)
Maximum Inrush Current
13A, 1ms (100–240 VAC)
15A, 1ms (240–264 VAC)
10A
Maximum Power
40VA
20W
Voltage Withstand (dielectric)
1 minute @ 1500VAC between primary, secondary, field ground
Insulation Resistance
> 10M
q
at 500VDC