DL06 Micro PLC User Manual; 3rd Edition Rev. E
4–7
Chapter 4: System Design and Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Chapter 4: System Design and Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
a
b
c
D
DL06 Port Pinouts
Configuring the DL06’s Comm Ports
This section describes how to configure the CPU’s built-in networking ports for either
MODBUS or
Direct
NET. This will allow you to connect the DL06 PLC system directly to
MODBUS networks using the RTU protocol, or to other devices on a
Direct
NET network.
MODBUS masters on the network must be capable of issuing the MODBUS commands
to read or write the appropriate data. For details on the MODBUS protocol, please refer
to the Gould MODBUS Protocol reference Guide (P1–MBUS–300 Rev. B). In the event
a more recent version is available, check with your MODBUS supplier before ordering the
documentation. For more details on
Direct
NET, order our
Direct
NET manual, part number
DA–DNET–M.
NOTE:
For information about the MODBUS protocol see the Group Schneider Web site at: www.
schneiderautomation.com. At the main menu, select Support/Services, Modbus, Modbus Technical Manuals,
PI-MBUS-300 Modbus Protocol Reference Guide or search for PIMBUS300. For more information about the
Direct
NET protocol, order our
Direct
NET user manual, part number DA–DNET–M, or download it free
from our Web site: www.automationdirect.com. Select Documentation/Misc./DA-DNET-M.
Communications Port 2
Port 2
Connects to HPP, DirectSOFT 5, operator
interfaces, etc.
15-pin, multifunction port, RS232C, RS422, RS485
Communication speed (baud): 300, 600, 1200,
2400, 4800, 9600, 19200, 38400
Parity: odd (default), even, none
Station Address: 1 (default)
8 data bits
1 start, 1 stop bit
Asynchronous, half-duplex, DTE
Protocol (auto-select): K-sequence (slave only),
DirectNET (master/slave), MODBUS (master/slave),
non-sequence/print/ASCII in/out
Port 1 Pin Descriptions
1 0V Power (-) connection (GND)
2 5V Power (+) connection
3 RXD Receive data (RS-232C)
4 TXD Transmit data (RS-232C)
5 5V Power (+) connection
6 0V Power (-) connection (GND)
Port 2 Pin Descriptions
1 5V
Power (+) connection
2 TXD Transmit data (RS-232C)
3 RXD Receive data (RS-232C)
4 RTS Ready to send (RS-232C)
5 CTS Clear to send (RS232C)
6 RXD- Receive data (-) (RS-422/485)
7 0V
Power (-) connection (GND)
8 0V
Power (-) connection (GND)
9 TXD+ Transmit data (+) (RS-422/485)
10 TXD- Transmit data (-) (RS-422/485)
11 RTS+ Ready to send (+) (RS-422/485)
12 RTS- Ready to send (-) (RS-422/485)
13 RXD+ Receive data (+) (RS-422/485)
14 CTS+ Clear to send (+) (RS-422/485)
15 CTS- Clear to send (-) (RS-422/485)
Communications Port 1
Port 1
Connects to HPP, DirectSOFT 5, operator
interfaces, etc.
6-pin, RS232C
Communication speed (baud): 9600 (fixed)
Parity: odd (fixed)
Station Address: 1 (fixed)
8 data bits
1 start, 1 stop bit
Asynchronous, half-duplex, DTE
Protocol (auto-select): K-sequence (slave only),
DirectNET (slave only), MODBUS (slave only)
DL06 Port Specifications
PORT1
PORT2
TERM
RUN STOP
PORT1
PORT2
R
R
PORT1
PORT2
1
6
3
4
2
5
1
5
6
10
11
15