DL06 Micro PLC User Manual, 3rd Edition, Rev. E
Chapter 2: Installation, Wiring, and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
2-32
D0–06AR I/O Wiring Diagram
The D0–06AR PLC has twenty AC inputs and sixteen relay contact outputs. The following
diagram shows a typical field wiring example. The AC external power connection uses four
terminals at the left as shown.
The twenty AC input channels use terminals on the bottom of the connector. Inputs are
organized into five banks of four. Each bank has a common terminal. The wiring example
below shows all commons connected together, but separate supplies and common circuits may
be used. The equivalent input circuit shows one channel of a typical bank.
LOGIC
Koyo
06
L L
L L
C0
C4
C2
X1
X3
X4
X6
X11 X13 X14
X16
X21 X23 N.C.
C1
C3
X2
X5
X7
X10 X12
X15 X17 X20 X22
X0
N.C.
L L
L L
L L
L L
L L
L L
AC(N) 24V
0V
N.C.
C1
C3
Y0
Y15
Y12
Y10
Y17
Y7
Y5
Y2
C0
C2
Y16
Y14
Y13
Y11
Y6
Y4
Y3
Y1
LG
G
AC(L)
D0-06AR
40VA
50-60Hz
PWR: 100-240V
2.0A
OUTPUT: 6-240V
50 - 60Hz 2.0A, 6 - 27V
Y
X
7 - 15mA
INPUT: 90 - 120V
0
1
2
3
4
5
6
7
10 11 12 13 14 15 16
17 20 21 22
23
OUTPUT point wiring
6-240
VAC
or
6-27
VDC
POWER
input wiring
100-240V
VAC
INPUT point wiring
90-120V
VAC
0
4
12
16
Points
Ambient Temperature (
˚
C/
˚
F)
0
32
10
50
20
68
30
86
40
104
50
122
55˚C
131˚F
Y0 - Y7
2.0A
Y10 - Y17
8
AR
Derating Chart for Relay Outputs
9$&
Equivalent Input Circuit
Equivalent Output Circuit
Typical Relay Life (Operations) at
Room Temperature
Voltage & Load
Type
Load Current
At 1A At 2A
24VDC Resistive
500K 250K
24VDC Inductive
100K 50K
110VAC Resistive
500K 250K
110VAC Inductive
200K 100K
220VAC Resistive
350K 200K
220VAC Inductive
100K 50K