
Miscellaneous Wiring Installation
The following voice terminals/telephones cannot be installed in an exposed
environment:
●
●
●
7300-type voice terminals connected to TN762 hybrid line circuit
packs
MET sets connected to TN735 MET line circuit packs
analog telephones connected TN746 analog line circuit packs.
PROTECTOR ORDERING INFORMATION
Description
361A (Carbon Block)
361E-W (Wide Gap Gas Tube)
3C1S (Solid State)
4B1C (Carbon Block with Heat Coil)
4B1E-W (Wide Gap Gas Tube with Heat Coil)
4C1S (Solid State with Heat Coil)
SCP-1 Sneak Current Protector
79A Fuse (sneak current protector)
Comcode
102 381 779
104 410 147
105 514 756
102 904 893
104 401 856
104 386 545
403 617 632
103 351 610
Digital Out-of-Building Voice Terminals
Protection is required at both building entrances for digital out-of-building
voice terminals. There are 6 different primary protectors that can be used
with the required secondary (data link) protector to protect digital voice
terminals in an out-of-building environment.
Primary protectors have a surge breakdown voltage range of 200 to 800 volts
at 100 volts per microsecond depending on the type of device. Sneak current
protection is also required. It can be provided by a 4-type protector or a 3-
type protector plus a separate sneak current protector. The 4-type primary
protector is equipped with a heat coil for sneak current protection. The 4-
type primary protector is the preferred device because it eliminates the need
to evaluate the interbuilding cable runs and its vulnerability to power cross
faults. When the 3-type primary protector is used, a separate sneak current
protector is required.
The secondary (data link) protector is required in addition to the primary
protector and is installed on the equipment side of the primary protector.
Table 4-B shows the recommended protectors.
4-41
Summary of Contents for System 75
Page 1: ...AT T AT T System 75 and System 75 XE Wiring...
Page 2: ...AT T AT T System 75 and System 75 XE Wiring 555 200 111 Issue 2 August 1989...
Page 16: ...System Wiring Figure 1 2 System Uniform Wiring Plan 1 7...
Page 17: ...CHAPTER 1 INTRODUCTION Figure 1 3 Sample Uniform Wiring Installation 1 8...
Page 29: ...CHAPTER 2 HARDWARE 66 110 Type Figure 2 1 Block Diagram of System 75 or 75 XE Installation 2 2...
Page 35: ...CHAPTER 2 HARDWARE 66 110 Type Figure 2 4 110A Type 100 Pair Terminal Block 2 8...
Page 36: ...110 Type Hardware Description Figure 2 5 110A Type 300 Pair Terminal Block 2 9...
Page 98: ...Typical System Equipment Room Floor Plans 3 15...
Page 143: ...CHAPTER 3 EQUIPMENT ROOM DESIGN 3 60...
Page 144: ...Equipment Room Hardware And Cabling Installation 3 61...
Page 162: ...Equipment Room Hardware And Cabling Installation 3 79...
Page 163: ...Equipment Room Hardware And Cabling Installation 3 80...
Page 197: ...Tables Table 4 A Recommended Protectors 4 42 v...
Page 212: ...Adjunct Powering 4 15...
Page 214: ...Adjunct Powering 4 17...
Page 216: ...Patch Cord Jumper Installation And Administration 4 19...
Page 241: ...CHAPTER 4 STATION WIRING 4 44...
Page 244: ...Miscellaneous Wiring Installation 4 47...
Page 246: ...Miscellaneous Wiring Installation 4 49...
Page 252: ...Miscellaneous Wiring Installation 4 55...
Page 254: ...Miscellaneous Wiring Installation 4 57...
Page 314: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION 5 41...
Page 324: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION 5 51...