CHAPTER 3. EQUIPMENT ROOM DESIGN
Installing Coupled Bonding Conductor (CBC) Grounding
A CBC must be tie-wrapped to all trunk cables. The CBC connects the
cabinet single-point ground block to the approved ground located
nearest the telephone company owned protector block at the building
entrance facility (Figure 3-59).
Note: The CBC is a conductor that is connected to ground and
run adjacent to the pairs in an inside wiring cable. The mutual
coupling between the bonding conductor and the cable pairs
reduces potential differences in terminating equipment. The
conductor consists of a No. 10 AWG wire that is tie-wrapped to the
inside wiring cable.
APPROVED GROUNDS
An approved ground is an acceptable medium for grounding the
building entrance protector, entrance cable shield, or single-point
ground of electronic PBX equipment. If more than one type of approved
ground is available on the premises, the grounds must be bonded
together as required in Section 250-81 of the National Electrical Code.
Metal Frame of the Building — the metal frame of the building where it
is effectively grounded by one of the following grounds: acceptable
metallic water pipe, concrete encased ground, or a ground ring.
Acceptable Water Pipe — a metal underground water pipe, at least 1/2
inch in diameter, in direct contact with the earth for at least 10 feet. The
pipe must be electrically continuous (or made electrically continuous by
bonding around insulated joints, plastic pipe, or plastic water meters) to
the point where the protector ground wire is connected. A metallic
underground water pipe must be supplemented by the metal frame of
the building, a concrete encased ground, or a ground ring. If these
grounds are not available, the water pipe ground can be supplemented
by one of the following types of grounds:
●
●
Metal underground gas piping system—an electrically continuous
metal underground gas piping system that is uninterrupted with
insulating sections or joints and without an outer nonconductive
coating
Other local metal underground systems or structures—local
underground structures such as tanks and piping systems
3-86
Summary of Contents for System 75
Page 1: ...AT T AT T System 75 and System 75 XE Wiring...
Page 2: ...AT T AT T System 75 and System 75 XE Wiring 555 200 111 Issue 2 August 1989...
Page 16: ...System Wiring Figure 1 2 System Uniform Wiring Plan 1 7...
Page 17: ...CHAPTER 1 INTRODUCTION Figure 1 3 Sample Uniform Wiring Installation 1 8...
Page 29: ...CHAPTER 2 HARDWARE 66 110 Type Figure 2 1 Block Diagram of System 75 or 75 XE Installation 2 2...
Page 35: ...CHAPTER 2 HARDWARE 66 110 Type Figure 2 4 110A Type 100 Pair Terminal Block 2 8...
Page 36: ...110 Type Hardware Description Figure 2 5 110A Type 300 Pair Terminal Block 2 9...
Page 98: ...Typical System Equipment Room Floor Plans 3 15...
Page 143: ...CHAPTER 3 EQUIPMENT ROOM DESIGN 3 60...
Page 144: ...Equipment Room Hardware And Cabling Installation 3 61...
Page 162: ...Equipment Room Hardware And Cabling Installation 3 79...
Page 163: ...Equipment Room Hardware And Cabling Installation 3 80...
Page 197: ...Tables Table 4 A Recommended Protectors 4 42 v...
Page 212: ...Adjunct Powering 4 15...
Page 214: ...Adjunct Powering 4 17...
Page 216: ...Patch Cord Jumper Installation And Administration 4 19...
Page 241: ...CHAPTER 4 STATION WIRING 4 44...
Page 244: ...Miscellaneous Wiring Installation 4 47...
Page 246: ...Miscellaneous Wiring Installation 4 49...
Page 252: ...Miscellaneous Wiring Installation 4 55...
Page 254: ...Miscellaneous Wiring Installation 4 57...
Page 314: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION 5 41...
Page 324: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION 5 51...