Equipment Room Hardware And Cabling Installation
●
●
Rod and pipe electrodes—a 5/8 inch (solid rod) or 3/4 inch
(conduit or pipe) electrode driven to a minimum depth of 8 feet
Plate electrodes—expose a minimum of 2 square feet of metallic
surface to the exterior soil.
Concrete Encased Ground — an electrode encased by at least 2
inches of concrete and located within and near the bottom of a concrete
foundation or footing in direct contact with the earth. The electrode
must be at least 20 feet of one or more steel reinforcing bars or rods 1/2
inch in diameter, or at least 20 feet of bare, solid copper, No. 4 AWG
wire.
Ground Ring — a buried ground that encircles a building or structure at
a depth of at least 2-1/2 feet below the earth’s surface. The ground ring
must be at least 20 feet of No. 2 AWG, bare, copper wire.
APPROVED FLOOR GROUNDS
Approved floor grounds are those grounds on the floor of a high-rise
building suitable for connection to the ground terminal in the riser closet
and to the PBX equipment single-point ground terminal. Such grounds
may be one of the following:
●
●
●
●
●
Building steel
The grounding conductor for the secondary side of the power
transformer feeding the floor
Metallic water pipes
Power feed metallic conduit supplying panel boards on the floor
A grounding point specifically provided in the building for the
purpose.
3-87
Summary of Contents for System 75
Page 1: ...AT T AT T System 75 and System 75 XE Wiring...
Page 2: ...AT T AT T System 75 and System 75 XE Wiring 555 200 111 Issue 2 August 1989...
Page 16: ...System Wiring Figure 1 2 System Uniform Wiring Plan 1 7...
Page 17: ...CHAPTER 1 INTRODUCTION Figure 1 3 Sample Uniform Wiring Installation 1 8...
Page 29: ...CHAPTER 2 HARDWARE 66 110 Type Figure 2 1 Block Diagram of System 75 or 75 XE Installation 2 2...
Page 35: ...CHAPTER 2 HARDWARE 66 110 Type Figure 2 4 110A Type 100 Pair Terminal Block 2 8...
Page 36: ...110 Type Hardware Description Figure 2 5 110A Type 300 Pair Terminal Block 2 9...
Page 98: ...Typical System Equipment Room Floor Plans 3 15...
Page 143: ...CHAPTER 3 EQUIPMENT ROOM DESIGN 3 60...
Page 144: ...Equipment Room Hardware And Cabling Installation 3 61...
Page 162: ...Equipment Room Hardware And Cabling Installation 3 79...
Page 163: ...Equipment Room Hardware And Cabling Installation 3 80...
Page 197: ...Tables Table 4 A Recommended Protectors 4 42 v...
Page 212: ...Adjunct Powering 4 15...
Page 214: ...Adjunct Powering 4 17...
Page 216: ...Patch Cord Jumper Installation And Administration 4 19...
Page 241: ...CHAPTER 4 STATION WIRING 4 44...
Page 244: ...Miscellaneous Wiring Installation 4 47...
Page 246: ...Miscellaneous Wiring Installation 4 49...
Page 252: ...Miscellaneous Wiring Installation 4 55...
Page 254: ...Miscellaneous Wiring Installation 4 57...
Page 314: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION 5 41...
Page 324: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION 5 51...