The Frequency Settings option displays a menu where the Event Settings for the frequency, in hertz, can be
configured.
This option displays a submenu where the Event Settings for the Total Real Power, in watts, can be configured.
This option displays a submenu where the Event Settings for the Total Power Factor can be configured.
This option displays a menu where an AC Power Disconnect Event can be configured.
Device Settings
This is a menu where you can configure the settings for your AC Power Device.
SiteBoss 571 - Device Settings for AC Power Monitor 1
A) Modbus Address [1]
B) PT Ratio [1]
C) CT Ratio [1]
D) Power Type [3P4W]
Modbus Address
Modbus address of the AC power monitor device. This is an integer setting with a range of 1 to 247. The default
value is 1.
PT Ratio
Ratio of secondary turns to primary turns on potential transformers (PT). This is an integer setting with a range of 1
to 10000. The default value is 1.
CT Ratio
Ratio of secondary turns to primary turns on current transformers (CT). This is an integer setting with a range of 1
to 10000. The default value is 1.
Power Type
This is a toggle to define the type of power being monitored. The possible values are 1P2W, 1P3W, 3P3W, and
3P4W. The default value is 3P4W.
Average Voltage Settings
This menu contains the options for configuring Average Voltage Events.
SiteBoss 571 - Average Voltage Settings for AC Power Monitor 1
A) Event Settings
B) System Reporting Settings
Enter your Selection: A
SiteBoss 571 - Average Voltage Event Settings for AC Power Monitor 1
A) Event Enabled [OFF]
B) Deadband [3.0]
C) Very High Event Settings [253.0] [] [520] [Info]
D) High Event Settings [243.8] [] [520] [Info]
E) Return to Normal Settings [-] [] [520] [Info]
F) Low Event Settings [216.2] [] [520] [Info]
G) Very Low Event Settings [207.0] [] [520] [Info]