Asentria SiteBoss 571 UserManual
Page 78
SiteBoss 571 - MAIN Voltage Sensor Settings
Device Number: 200 Device ID: 0C000000 Device Name: INTERNAL
A) Voltage Sensor Enabled [OFF]
B) Deadband (mV) [20]
C) Very High Event Settings [58000] [] [190] [Info]
D) High Event Settings [56000] [] [190] [Info]
E) Return to Normal Settings [-] [] [190] [Info]
F) Low Event Settings [44500] [] [190] [Info]
G) Very Low Event Settings [42500] [] [190] [Info]]
Voltage Sensor Enabled
This is an ON/OFF toggle to enable this sensor.
Deadband
This is the range (in millivolts) on either side of a voltage setting that prevents the event from repeatedly going in
and out of the "alarm state" as the actual voltage fluctuates above and below the voltage setting.
Very High / High / Low / Very Low Event Settings
These options display menus where the voltage at each level can be configured to alarm along with the action(s) to
occur, trap number, and class. In the case of Very High or High levels, the alarm will occur as the voltage rises
above the setting. In the case of Low or Very Low, the alarm will occur as the voltage drops below the setting.
This option displays a menu where the optional action definition for events as they return to a normal state can be
configured.
Very High / High / Low / Very Low Current Sensor Event Settings
The menu for setting Very High Event Value settings is shown. The menus for High/Low/Very Low are identical.
SiteBoss 571 MAIN Voltage Sensor Event
Device Number: 200 Device ID: 0C000000 Device Name: INTERNAL
A) Very High Event Value (mV) [58000]
B) Very High Event Actions []
C) Very High Event Trap Number [190]
D) Very High Event Class [Info]
Very High Event Value
This option sets the voltage (in millivolts) at which the Very High Event Actions will be triggered.
Very High Event Actions
This will displays the Actions List, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to the
Very High Event Trap Number
This sets the trap number which can be useful when using SNMP trap managers that employ a trap numbering
system to help identify incoming traps. The default trap number for Main Voltage Sensor Events is 190, but any
number in the alternate range of 1000
– 1199 can be used.
Very High Event Class
Set the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this event.
Return to Normal Settings
This menu is used to configure actions for the SiteBoss to take when the voltage readings return to the defined
normal range.