SiteBoss 571 - Internal Temperature Event
A) Temperature Sensor Enabled [OFF]
B) Sensor Values Represented in [FAHRENHEIT]
C) Temperature Deadband [3.0]
D) Very High Event Settings [100.0[] [120] [Info]
E) High Event Settings [80.0][] [120] [Info]
F) Return to Normal Settings [-] [] [120] [Info]
G) Low Event Settings [50.0][] [120] [Info]
H) Very Low Event Settings [30.0][] [120] [Info]
Temperature Sensor Enabled
This is an ON/OFF toggle to enable the temperature sensor.
Sensor Values Represented In
This field toggles to either FAHRENHEIT or CELSIUS for the desired temperature scale. The default is
FAHRENHEIT.
Temperature Deadband
The Deadband is a range, in degrees, on either side of a temperature setting that prevents the event from
repeatedly going in and out of the "alarm state" as the actual temperature fluctuates above and below the
temperature setting. The default is 3 degrees.
Very High / High / Low / Very Low Event Settings
These menu options display menus where the temperature at each level can be configured to alarm along with the
action(s) to occur, trap number, and class. In the case of Very High or High levels, the alarm will occur as the
temperature rises above the setting. In the case of Low or Very Low, the alarm will occur as the amperage drops
below the setting.
This option displays a menu where the actions for events as the temperature returns to a normal state can be
configured.
Very High / High / Low / Very Low Event Settings Setup
The menu for setting Very High Temperature settings is shown. The menus for High/Low/Very Low are identical.
In the case of Very High or High levels, the alarm will occur as the temperature rises above the setting. In the case
of Low or Very Low, the alarm will occur as the temperature drops below the setting.
SiteBoss 571 - Internal Temperature Event Settings
A) Very High Event Temperature [100.0]
B) Very High Event Actions []
C) Very High Event Trap Number [120]
D) Very High Event Class [Info]
Very High Event Temperature
Set the temperature at which the Very High Event Actions will be triggered.
Very High Event Actions
This option displays the Actions List, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to the
Very High Trap Number
This field sets the trap number which can be useful when using SNMP trap managers that employ a trap
numbering system to help identify incoming traps. The default trap number for Temperature Events is 120, but any
number in the alternate range of 1000
– 1199 can be used.