Asentria SiteBoss 571 UserManual
Page 90
Deadband
The Deadband option allows you to set a range that prevents the event from repeatedly going in and out of the
"alarm state" as the current reading fluctuates above and below the alarm setting. The default value is 1.0.
Very High / High / Return to Normal / Low / Very Low Average Voltage Event Settings
These options display submenus where the event action settings can be configured for each event level.
SiteBoss 571 - Average Current Event Settings for AC Power Monitor 1
A) Very High Event Value [30.0]
B) Very High Event Actions []
C) Very High Event Trap Number [521]
D) Very High Event Class [Info]
Very High / High / Low / Very Low Event Volume
These fields are used to set the average current, in amps, which triggers the Event Action(s). The range for each
tier setting is 0 to 1000 with the defaults shown above in the screen shot.
Very High / High / Return to Normal / Low / Very Low Event Actions
These fields are used to set the action(s) that will be triggered when the average current crosses the set threshold.
This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have
been configured. Refer to
Very High / High / Return to Normal / Low / Very Low Event Trap Number
These fields are used to set the trap number which can be useful when using SNMP trap managers that employ a
trap numbering system to help identify incoming traps. The default trap number for all Average Current Events is
521, but any number in the alternate range of 1000
– 1199 can be used.
Very High / High / Return to Normal / Low / Very Low Event Class
These fields are used to set the class for the event. When this option is selected, a list of the classes previously
defined in the
is displayed. Select one to be assigned to this event. The default is Info.
System Reporting Settings
The System Reporting Settings are not functional.
Frequency Settings
The Frequency Settings menu is where the Event Settings for the frequency variations can be configured.
SiteBoss 571 - Frequency Settings for AC Power Monitor 1
A) Event Settings
B) System Reporting Settings
Enter your Selection: A
SiteBoss 571 - Frequency Event Settings for AC Power Monitor 1
A) Event Enabled [OFF]
B) Deadband [0.5]
C) Very High Event Settings [52.0] [] [522] [Info]
D) High Event Settings [51.0] [] [522] [Info]
E) Return to Normal Settings [-] [] [522] [Info]
F) Low Event Settings [49.0] [] [522] [Info]
G) Very Low Event Settings [48.0] [] [522] [Info]
Event Enable
This is an ON/OFF toggle to enable the Frequency Event. The default setting is OFF