Name
Use this field to set the name of the specific output. This name will be displayed in the status and control menus
(Maximum length 60 chars). The default setting is unnamed.
State
This setting toggles to set whether the output state should be ON or OFF. When you toggle this field you will get a
challenge question, "Are you sure you want to make this output ON/OFF (y/n)?" This setting will not change
without a positive response to the challenge question. The default setting is ON.
Note:
Ensure the power distribution lines are clear when powering on an output. A "Y" response to the
challenge question will engage the power immediately.
Remarque: S'assurer que les lignes de distribution d'énergie sont clairement lors de la mise sur une sortie.
Une réponse «Y» à la question de défi engager immédiatement le pouvoir.
Active Alias
This is an alphanumeric field to customize the name of the Active (ON) state. The default setting is On. (Maximum
length 60 chars)
Inactive Alias
This is an alphanumeric field to customize the name of the Inactive (OFF) state. The default setting is Off.
Active Color
This field is a hex color code for the color that will be displayed in the web interface on the EventSensor Status
Screen whenever a relay point is in the Active (ON). The default Active Color is red (#E00303).
Inactive Color
This field is a hex color code for the color that will be displayed in the web interface on the EventSensor Status
Screen whenever a relay point is in the Inactive (OFF). The default Inactive Color is green (#2FCF17).
Active/Inactive Event Actions
Choosing this option displays the Actions List, a menu where the action string for the event is configured. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to the
Active/Inactive Trap Number
These fields set the trap number which can be useful when using SNMP trap managers that employ a trap
numbering system to help identify incoming traps. The default trap number for power output events is 150, but any
number in the alternate range of 1000
– 1199 can be used.
Active/Inactive Class
This option is to set the class for the event. When this option is selected, a list of the classes previously defined in
the
is displayed. Select one to be assigned to this event. The default is Info.
Load Shedding Settings
The load shedding feature allows individual configuration of power outputs to selectively shut off power to
connected equipment after mains power is lost. The settings that are configured in this menu will begin to function
if an SNMP trap is received from the rectifier indicating the mains power is lost. The SiteBoss retrieves the battery
voltage from the rectifier via SNMP every 10 seconds. The power can be shut off by time delay or if the battery
voltage drops to a preconfigured level.
Once an output is shut off due to load shedding, it remains shut off until after the load shedding function goes back
into the normal state. This can happen because mains power is restored or if load shedding is aborted. Outputs
are restored after a user-adjustable delay, which defaults to one minute. In the normal state, the host unit stops
retrieving the battery voltage from the rectifier.
For more information see the
chapter, the
on the
Asentria Product Information Portal or contact