SiteBoss 571 - Volume Event Settings
A) Very High Event Volume [180.0]
B) Very High Event Actions []
C) Very High Event Trap Number [519]
D) Very High Event Class [Info]
Very High / High / Low / Very Low Event Volume
Set the fuel volume (in volume units) threshold at which the Event Action(s) will be triggered.
Very High / High / Return to Normal / Low / Very Low Event Actions
Set the action(s) that will be triggered once the fuel level crosses the threshold. This field will be empty [ ] if
no actions have been configured, and will show [*SET*] if one or more actions have been configured. Refer to
Very High / High / Return to Normal / Low / Very Low Event Trap Number
Set the trap number which can be useful when using SNMP trap managers that employ a trap numbering system
to help identify incoming traps. The default trap number for all fuel volume events is 519, but any number in the
alternate range of 1000
– 1199 can be used.
Very High / High / Return to Normal / Low / Very Low Event Class
Set the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed. Select one to be assigned to this event. The default is Info.
Disconnect Event Settings
This menu is for configuring alarm notifications of the fuel sensor being disconnected.
SiteBoss 571 - Disconnect Event Settings for Fuel Sensor 1
A) Event Enabled [OFF]
B) High Value [0]
C) Low Value [0]
D) Event Actions []
E) Event Trap Number [515]
F) Event Class [Info]
G) Normal Actions []
H) Normal Trap Number [515]
I) Normal Class [Info]
Event Enabled
This is an ON/OFF toggle to enable Volume Events. The default setting is OFF.
High / Low Value
These menu options are used to set the High end and low end of normal for the analog input associated with the
fuel sensor. If the input value falls outside the delineated range, then the sensor is considered "disconnected". If
both high and low values are set to 0 (the default value), then the sensor will always be considered "connected".
Event Actions
This menu option is used to set the action(s) that will be triggered if the fuel level sensor is disconnected. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have
been configured. Refer to
Event Trap Number
This option is used to set the trap number which can be useful when using SNMP trap managers that employ a
trap numbering system to help identify incoming traps. The default trap number for disconnect events is 515, but
any number in the alternate range of 1000
– 1199 can be used.
Event Class
This option is used to set the class for the event. This user-configurable optional setting defines the severity of
the event. An event severity is defined in the user configurable