Asentria SiteBoss 571 UserManual
Page 80
Deadband
The Deadband is the range (in milliamps) on either side of an amperage setting that prevents the event from
repeatedly going in and out of the "alarm state" as the actual amperage fluctuates above and below the amperage
setting.
Very High / High / Low / Very Low Event Settings
These menu options display menus where the amperage at each level can be configured to alarm along with the
action(s) to occur, trap number, and class. In the case of Very High or High levels, the alarm will occur as the
amperage rises above the setting. In the case of Low or Very Low, the alarm will occur as the amperage drops
below the setting.
This option displays a menu where the event actions for when the sensor readings return to a normal state can be
configured.
Very High / High / Low / Very Low Current Sensor Event Settings
The menu for setting Very High Event Value settings is shown. The menus for High/Low/Very Low are identical.
SiteBoss 571 Current Sensor Event for Output 1
Device Number: 200 Device ID: 0C000000 Device Name: INTERNAL
A) Very High Event Value (mA) [12000]
B) Very High Event Actions []
C) Very High Event Trap Number [180]
D) Very High Event Class [Info]
Very High Event Value
This option sets the amperage (in milliamps) at which the Very High Event Actions will be triggered.
Very High Event Actions
This displays the Actions List, a menu where the action string for the event is configured. This field will be empty
[ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured. Refer to
the
Very High Event Trap Number
Set the trap number which can be useful when using SNMP trap managers that employ a trap numbering system
to help identify incoming traps. The default trap number for Current Sensor Events is 180, but any number in the
alternate range of 1000
– 1199 can be used.
Very High Event Class
Set the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this event.
Return to Normal Settings
This menu is used to configure actions for the SiteBoss to take when the current readings return to the defined
normal range.
SiteBoss 571 - Current Sensor Event for Output 1
Device Number: 200 Device ID: 0C000000 Device Name: INTERNAL
A) Return to Normal Event Actions []
B) Return to Normal Event Trap Number [180]
C) Return to Normal Event Class [Info]
Return to Normal Event Actions
This selection displays the Actions List, a menu where the action string for the event is configured. This field will
be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to the