Date Time :: SiteName :: Sensor Pod/Bank name :: Sensor Point Name :: Alarm Alias
For example, a typical SMS message for a temperature alarm might look like the following:
09/25 15:59 :: San Diego Site #12 :: Sensor Pod 12 :: Cabinet Temp :: Temperature Very High
SMS alarm messaging has the following limitations:
The user cannot specify the order of event message items
The user CAN specify which items are included in event message using the existing mechanism
The event class is not included
If the event message is too large to fit into the allowed SMS message size, it will be broken up into multiple
SMS messages
Pager Alarms
Note:
requires dial-up modem, which is not supported by the S571.
Pager alarm messages contain a concatenated alarm string, which follows the format of:
Date Time :: SiteName :: Sensor Pod/Bank name :: Sensor Point Name :: Alarm Alias
For example, a typical Pager notification for a temperature alarm might look like the following:
09/25 15:59 :: San Diego Site #12 :: Sensor Pod 12 :: Cabinet Temp :: Temperature Very High
Power Outputs and Relays as Alarm Action
Power outputs can be used to turn on or off attached devices. Outputs can be toggled based on sensor readings,
data events, the Setup menu Power Output Control option, or even remotely by SNMP.
Relays can be used to open or close part of a circuit of your design or part of another product. You can use relays
on Expansion Cards installed in the S571 or built into EventSensors, to control these devices. Relays can be
toggled based on sensor readings, data events, or even remotely by SNMP.
Caution:
Do not exceed maximum ratings for any outputs. Power outputs and relays are only
designed for DC power distribution with SELV limits (60VDC Max), and are not intended to control AC
powered devices. Improper use outside the guidelines of this manual could cause injury.
Attention: Ne pas dépasser notes maximales pour toutes les sorties. Sorties de puissance et des relais
sont uniquement conçus pour la distribution de courant continu avec des limites SELV (60VDC Max),
et ne sont pas destinés à contrôler les appareils alimentés en courant alternatif. Une mauvaise
utilisation en dehors des lignes directrices de ce manuel peut provoquer des blessures.
9 standard 10A outputs
1 optional 30A output
Max switched voltage: 60V
Max switched voltage: 60V
Max switched current: 10A
Max switched current: 30A
Max switched power: 600W
Max switched power: 1800W
Action Definition
Output actions are defined in the
and below. Output definitions are somewhat more complicated than
other sensors in that they must declare the action to perform, which sensor the output is on, and which output on
that sensor to switch.
Note:
All S571 internal power distribution outputs are on EventSensor number 200 (internal).