Chapter 4: Maintenance
1X-E4 Series Installation Manual
69
Battery maintenance
Compatible batteries
The control panel requires two 12V, 7.2 or 12 Ah rechargeable sealed lead-acid
batteries. Compatible batteries for this product are:
• BS127N-A (7.2 Ah)
• BS130N (12 Ah)
• Fiamm FG20721/2 (7.2 Ah)
• Fiamm FG21201/2 (12 Ah)
• Yuasa NP7-12 (7.0 Ah)
• Yuasa NP12-12 (12 Ah)
Troubleshooting batteries
Battery supply and battery fuse faults are indicated by a flashing Supply Fault
LED. If this LED is flashing, check the following:
• That the battery cables are in good condition
• That the battery cables are connected securely and correctly at the battery
and at the control panel PCB
If the cables are in good condition and all connections are correct, then the
batteries should be replaced immediately.
Replacing batteries
Batteries must be replaced periodically as recommended by the battery
manufacturer. The useful life of the battery is approximately four years. Avoid the
total discharge of the batteries. Always use the recommended replacement
batteries.
To replace the batteries:
1. Disconnect and remove the existing batteries from the cabinet.
2. Install and connect the replacement batteries using the bridge provided.
Observe correct polarity.
3. Dispose of the batteries as required by local or regional regulations.
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...