Chapter 3: Configuration and commissioning
1X-E4 Series Installation Manual
45
Zone delay
Use this menu to configure zone delays (on or off), for each zone in your fire
alarm and evacuation system. If the zone delay is ON, for alarms reported from
this zone, any output activation (fire routing and expansion board outputs) will
consider delay before activation. The default setting for all zones is ON.
For a stand-alone control panel, you specify the zone using the zone number.
When the control panel is in a fire network, unique zone numbers are created by
defining a unique starting number for the first zone in each panel. For example, if
the first zone is numbered 101, then zone 04 will have the number 104.
In a fire network, if the control panel is configured to activate with remote zones,
you can enter “others” to select the delay for remote zones.
See the topic “Fire network and repeaters configuration” on page 56 for further
details.
To configure the zone delay:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
— or —
Select “others” to select the remote zones.
The Zone alarm LED flashes fast to indicate that the corresponding zone
configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Configured delays are applied when the alarm is
reported from this zone.
Configured delays are not applied. Outputs activate
immediately when the alarm is reported from this zone.
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...