Functional tests
Create a short and open circuit in the zone to test fault reporting for each.
Activate a manual call point to test manual alarm reporting. The control panel
should override any configured delays and activate alarm notification devices and
fire routing (where applicable) immediately.
Activate a detector to test automatic alarm reporting. The control panel should
initiate any configured delays and activate alarm notification devices and fire
routing (where applicable) once the delay time has elapsed.
Using a multimeter, verify that the fault relay is activated when a fault is reported
and that the alarm relay is activated when an alarm is reported.
Activate all sounders by pressing the All Sounders Start button and the Confirm
button to test evacuation alarm reporting.
Response times
Response times for standard events are as follows.
Table 24: Response times for standard events
Event
Response time
Alarm
Less than 3 seconds
Zone fault
Less than 30 seconds
Sounder fault
Less than 30 seconds
Fire routing fault
Less than 30 seconds
Expansion board fault
Less than 100 seconds
Network fault
Less than 100 seconds
Earth fault
Less than 100 seconds
Battery charger fault
Less than 100 seconds
No batteries found fault
Less than 3 minutes
Mains fault
Less than 3 minutes
Out of service fault
Less than 100 seconds
Fuse/protection fault
Less than 3 minutes
System fault
Less than 100 seconds
Battery high resistance fault Less than 4 hours
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...