Chapter 2: Installation
14
1X-E4 Series Installation Manual
Connecting supervised inputs
Connect supervised input switches to INPUT1 and INPUT2, as shown in Figure 8
below.
Figure 8: Connecting supervised inputs
Nominal resistance values (including any cable resistance) are shown in Table 8
below.
Table 8: Nominal resistance values for supervised inputs
Input function
Input
Value
[1]
State
Fire routing acknowledgement
(type 1, 100 seconds)
1
≤ 220 Ω
Short circuit
> 220 Ω to 8 kΩ
Active [2]
> 8 kΩ to 10 kΩ
Fault [3]
> 10 kΩ to 20 kΩ
Standby
> 20 kΩ
Open circuit
Fault warning output: open circuit
supervision [4]
2
≤ 9 kΩ
Standby
> 9 kΩ
Fault (open)
[1] Values between each state may vary, depending on tolerance.
[2] For EN 54-
13 compliance, the active impedance should be in the range of 220 Ω to 3.9 kΩ.
[3] High impedance fault.
[4] For the open circuit supervision of the fault warning output with the input, a 2010-FS EOL
board must be installed. See “Connecting the fault warning output” on page 17.