Chapter 3: Configuration and commissioning
1X-E4 Series Installation Manual
43
Sounder re-sound
Use this menu to configure the sounder re-sound, on or off. This determines
sounder operation in a fire alarm event when sounders have been silenced and
a new alarm event is reported. The default setting is ON.
To configure the sounder re-sound:
1. Set the display as shown below, and then press Enter.
The All Sounders Start LED flashes fast to indicate that the sounder re-sound
configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
The sounders re-sound if a new fire alarm event is
reported from a different zone.
The sounders do not re-sound if a new fire alarm event
is reported from a different zone.
Note: For new fire alarm events in the same zone, sounders will always re-
sound if the first alarm is reported by a detector and the new alarm is
reported by a manual call point.