Chapter 3: Configuration and commissioning
44
1X-E4 Series Installation Manual
Zone configuration
Use this menu to configure zone settings for each zone in your fire alarm and
evacuation system. The default setting for each operating mode is included in
Appendix A “Configuration presets” on page 79.
To configure the zone:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The Zone fault/test/disable LED flashes fast to indicate that the corresponding
zone configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Passive end-of-line
Active end-of-line [1]
Passive end-of-line with CleanMe [1]
Active end-of-line with CleanMe [1]
Intrinsically-safe zone [1][2]
[1] Option not available if EN 54-13 supervision is enabled.
[2] By default, even zones are configured as manual and odd zones are set
as automatic.