Chapter 3: Configuration and commissioning
34
1X-E4 Series Installation Manual
Basic default configuration
Use this menu to select common operating mode configuration presets. The
default setting is 41.
To select an operating mode configuration preset:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
See Table 19 below for descriptions of the presets.
3. Press Enter.
4. Save your changes.
A selected list of operating mode configuration presets is shown below. For a
detailed list of all available configuration presets and characteristics, see
Appendix A “Configuration presets” on page 79.
Table 19: Common operating mode configuration presets (EN 54-13 disabled)
Display
Operating mode
Zone end-of-line
Zone type
41 (default)
4E (four evacuation areas) Passive
Odd zones: Automatic
Even zones: Manual
43
2E (two evacuation areas) Passive
Odd zones: Automatic
Even zones: Manual
45
1E (one evacuation area)
Passive
Odd zones: Automatic
Even zones: Manual
The operating mode is indicated by the first digit in the display and the
configuration type by the second digit. If a custom configuration has been applied
(via the advanced configuration menu), then the second digit is a zero, as shown
below.
Display
Configuration
41
NEN 2575 four evacuation areas preset configuration
43
NEN 2575 two evacuation areas preset configuration
45
NEN 2575 one evacuation area preset configuration
40
NEN 2575 custom configuration
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...