Chapter 3: Configuration and commissioning
54
1X-E4 Series Installation Manual
Table 21: Expansion board A configuration options
Display
Description
Value
Module A function
01 to 94 [1]
Module A output 1 delay
00 to 10 minutes
Module A output 2 delay
00 to 10 minutes
Module A output 3 delay
00 to 10 minutes
Module A output 4 delay
00 to 10 minutes
[1] Available values depend on the type of expansion board installed and the
supervision selected. See Appendix A “Configuration presets” on page 79.
Expansion board function
Use this menu to configure the expansion board function. The default value
depends on panel configuration. For most configurations, the default value is 01.
For evacuation panels configured for EN 54-13, the default is 05. For the
available presets, see Appendix A “Configuration presets” on page 79.
To configure the expansion board function:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED on the control panel interface and the
ON LED on the expansion board flashes fast to indicate that the module
function configuration menu is active.
2. Select a value from 01 to 94 using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.