Chapter 3: Configuration and commissioning
60
1X-E4 Series Installation Manual
Display
Description
Value
Firenet repeater map
Submenu: 1 – 32
Values: On/OFF
Default: ON for nodes 1 and 2, OFF for the rest
Firenet remote output control
On/ OFF
Default: OFF
[1] The basic configuration setting can be replaced by a customized set of specific panels for
communication, called a firenet map (nM), and a set of panels to be repeated, called a firenet
repeater map (rM). If the configuration is changed by modifying nM or rM, the value displayed for
firenet number of nodes (nn) is Cu, indicating a custom network configuration.
Configuring firenet and repeater maps
If the control panels in the system do not have all the node IDs numbered
consecutively (starting from 1) or if the control panels do not repeat information
from all other panels, then configure the nM (Firenet map) and rM (Firenet
repeater map).
Firenet map (nM) configuration
Any control panel in the fire network can be configured to show remote zone
events and react as if the events were coming from the local zones, for the zones
that are within the range of the panel. The range of zones in the panel is
determined with the initial zone (offset) and the control panel type. The global
zone numbers can be 1 to 9999.
This means that, for a four-zone evacuation panel, the initial zone number can
range from 1 to 9996. A four-zone evacuation panel with an initial zone number
of 100 has zones 100 through 103.
The firenet map (nM) defines all the control panels that communicate with the
configured panel. This lets you create subnetworks in the fire network. For
example, if you have four panels in a fire network as follows:
• Panel ID 1 with nM active for nodes 1 and 2
• Panel ID 2 with nM active for nodes 1 and 2
• Panel ID 20 with nM active for nodes 20 and 32
• Panel ID 32 with nM active for nodes 20 and 32
Panels 1 and 2 will see each other in one sub-network and panels 20 and 32 will
be each other in a different sub-network. Only a firenet wiring open-loop fault for
class A networks will be shared between the two sub-networks.
Repeater map (rM) configuration
Any control panel in the fire network can repeat the information of other nodes
that form part of its firenet map.
A unique panel or several panels can be repeated at the same time (including
addressable panels) by defining the repeater map.
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...