Chapter 5: Technical specifications
74
1X-E4 Series Installation Manual
Table 30: Output specifications
Output termination
Class B outputs (default)
Class A outputs
15 kΩ 5% end
-of-line resistor
4.7 kΩ 1/4W 1% end
-of-line resistor
Sounder/fire routing/fault warning outputs [1]
Supervised
Current per output
Voltage in standby (EN 54-13 disabled)
Voltage in standby (EN 54-13 enabled)
Voltage in alarm
For open and short circuit
500 mA max. at 25ºC
385 mA max. at 40ºC
−11.5 VDC max.
−8.4 VDC max.
+21 VDC min.
+28 VDC max.
Alarm relay output
Number of potential-free outputs
Commutation current
1
2 A at 30 VDC max.
Fault relay output
Number of potential-free outputs
Commutation current
Default state
1
2 A at 30 VDC max.
Energized (fail to safe)
Auxiliary 24 VDC output
Voltage
Current
24 VDC nominal
28 VDC max.
21 VDC min.
250 mA max.
[1] The number of available outputs depends on the control panel model, supervision type, and
operating mode. See “Operating mode presets” on page 80 for more information.