Chapter 2: Installation
1X-E4 Series Installation Manual
17
Connecting fire routing equipment to supervised outputs
Connect fire routing equipment as shown in Table 13 below.
Table 13: Connecting fire routing equipment
Operating mode
Output class
Fire routing
(automatic)
Fire routing (manual)
NEN 2575 (EN 54-13
disabled)
Class B
OUT5
OUT6
NEN 2575 (EN 54-13
enabled)
Class A
OUT5, OUT6
OUT5, OUT6
Note:
Fire routing in EN 54-13 operating modes makes no distinction between
automatic and manual alarms. If this feature is required, install a 2010-1-SB
expansion board and use separate outputs for each alarm type.
Connecting the fault warning output to external equipment
Caution:
This connection is mandatory to comply with EN 54-2 Clause 8.9 (Fault
Warning Routing Equipment).
Note:
This feature is only available in EN 54-13 mode with a 2010-1-SB
supervised expansion board configured to preset 35. See “Expansion board
presets” on page 82.
Connect the external equipment to the OUT3 output on the 2010-1-SB
supervised board. The wiring must be returned back to the control panel to the
2010-FS-EOL user supervisory board connected to INPUT2, as shown below.
Figure 9: Connecting to fault warning output
1. 2010-FS-EOL user board
2. Control panel PCB connectors
3. 2010-1-SB expansion board connectors
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...