Chapter 2: Installation
12
1X-E4 Series Installation Manual
Connecting detectors
Connect detectors as shown in Figure 4, Figure 5, Figure 6, and Figure 7 starting
on page 9.
The panel supports conventional detectors. To guarantee optimal operation, use
the detectors specified in the compatibility list. For more information on fire
detectors, see Chapter 5 “Technical specifications” on page 71.
Connecting manual call points
Connect manual call points in parallel, as shown in Figure 4, Figure 5, Figure 6,
and Figure 7 starting on page 9. Each zone circuit can support up to 32 manual
call points.
Manual call points must have a resistance installed in series with the normally
open (NO) contact to avoid short-circuit faults and to allow the control panel to
identify the origin of the alarm (automatic or manual). Note that many of the
MCPs in the compatibility list already include this resistor.
The resistance required will depend on the zone type as shown in Table 5 below.
Table 5: MCP resistances
Zone type
Manual call point resistance
[1]
Standard / active end-of-
line
EN 54-13
Intrinsically safe
Mixed
100 Ω
Not supported
Not supported
Manual
100 to 680 Ω
100 to 470 Ω
250 to 560 Ω
[1] Resistance must be rated at 1 W minimum.
Note:
The default zone detection settings for each operating mode can be found
in Appendix A “Configuration presets” on page 79. To change the zone detection
setting, see “Advanced configuration” on page 40.
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...