Chapter 3: Configuration and commissioning
64
1X-E4 Series Installation Manual
Commissioning the control panel
Once all installation, connection, and configuration requirements have been
checked as described above, the control panel can be powered up.
Normal startup
After starting up the control panel, normal status (standby) is indicated as follows:
• The Supply LED is steady
• The Fire Routing Delay LED is steady (if a delay has been enabled)
If any other indicators are on, check your installation thoroughly before
proceeding.
Fault startup
In accordance with EN 54-2, the control panel has a special startup sequence
used after an internal fault has been detected by the control panel.
This is indicated as follows:
• The General Fault LED flashes fast
• The System Fault LED flashes slow
When this happens:
1. Enter the Operator user level password.
2. Press the Reset button to reset the control panel.
If the fault status persists after reset, the control panel aborts the startup
sequence and turns on the System Fault LED.
When this happens, check all control panel connections and configuration, as
described in “Before commissioning the control panel” on page 63.