Chapter 3: Configuration and commissioning
1X-E4 Series Installation Manual
35
EN 54-13 supervision mode
Use this menu to select the zone supervision mode (EN 54-13 supervision
enabled or disabled). By default EN 54-13 zone supervision is disabled.
To configure the supervision mode:
1. Set the display as shown below, and then press Enter.
The Sounder and Fire Routing Fault/Disable/Test LEDs and all zone LEDs
flash quickly to indicate that the supervision mode configuration menu is
active.
2. Select the supervision mode using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Default setting. EN 54-13 zone supervision is disabled
and all outputs are configured as Class B.
EN 54-13 zone supervision is enabled and all outputs
are configured as Class A.