Chapter 3: Configuration and commissioning
56
1X-E4 Series Installation Manual
Fire network and repeaters configuration
This section describes how to configure a fire network of conventional control
panels in order to:
• Connect repeaters (any conventional control panel can be configured to
operate as a repeater)
• Create a fire network of conventional control panels, when you need
additional conventional zones in your system
• Create a network including compatible addressable control panels, to add
more features to your fire alarm and evacuation system (e.g. logging events,
complex output activation controlled by the addressable system, remote
monitoring)
When a conventional panel is connected to a fire network it normally displays the
status of one or more panels in the network (depending on repeater configuration
settings). To display information for only that panel, press the Enter key for 3
seconds to provide a temporary, 30-second display of the local status indications.