Connecting the batteries
The control panel requires two 12 V, 7.2 or 12 Ah rechargeable, sealed, lead-
acid batteries (see “Compatible batteries” on page 69).
Batteries must be installed in series, at the base of the control panel cabinet. Use
the battery lead and bridge provided and connect batteries to the BATT
connector on the control panel PCB, as shown below. Polarity must be observed.
Note:
If the control panel indicates a Supply Fault, then the batteries may need
to be replaced. See “Battery maintenance” on page 69.
Figure 12: Connecting the batteries
Caution:
Risk of equipment damage. No other equipment may be connected to
the BATT connector.
Powering auxiliary equipment (24 VDC auxiliary output)
Connect auxiliary equipment that requires 24 VDC power to the 24 AUX
terminals as shown in Figure 4 on page 9. The 24 VDC auxiliary output is
supervised for short circuit and voltage output level.
WARNING:
Never use the auxiliary output to power expansion boards connected
to the same control panel as this might damage the control panel hardware.