Chapter 2: Installation
8
1X-E4 Series Installation Manual
Connections
WARNING:
Electrocution hazard. To avoid personal injury or death from
electrocution, do not make any control panel or system connections while the
control panel is connected to the mains power supply.
Recommended cables
Recommended cables for optimal system performance are shown in the table
below.
Table 2: Recommended cables
Cable
Cable description
Maximum cable length
Mains cable
3 x 1.5 mm²
N/A
Input, output, auxiliary 24V,
relay, expansion board
12 to 26 AWG (3.31 to 0.13 mm²)
Twisted-
pair (max. 40 Ω / 500 nF)
2 km
Zone circuit cable (mixed zone) 12 to 26 AWG (3.31 to 0.13 mm²)
Twisted-
pair (max. 40 Ω / 500 nF)
2 km
Zone circuit cable (automatic or
manual zones)
12 to 26 AWG (3.31 to 0.13 mm²)
Twisted-
pair (max. 55 Ω / 500 nF)
2 km
Fire network cable
Twisted-pair, Cat 5
12 to 26 AWG (3.31 to 0.13 mm²)
1.2 km
Note:
Other types of cable may be used subject to site-specific EMI conditions
and installation testing.
Use 20 mm cable glands to ensure clean and secure connections at the control
panel cabinet. All cables should be fed through the cable guides in the cabinet
housing to eliminate movement.