Chapter 3: Configuration and commissioning
1X-E4 Series Installation Manual
53
Expansion board configuration
Adding an expansion board
Use this menu, available from the basic or advanced configuration menus, to
configure the number of installed expansion boards. The default value is 00.
Up to four expansion boards can be installed in the evacuation control panel.
Note:
To maintain regulatory compliance, only three expansion boards can be
installed when a fire network board is installed.
To add an expansion board:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED flashes fast to indicate that the
module configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Expansion board configuration
Expansion board labels
For configuration purposes expansion boards are labeled A and B (for two- and
four-zone control panels) or A, B, C, and D (for eight-zone control panels).
The label for a given module is defined by its position (left to right) in the control
panel cabinet, The first expansion board installed is module A, the second B, etc.
See your expansion board installation sheet for installation instructions.
Expansion board function and delay configuration
Once an expansion board is installed and added to the control panel
configuration, the following additional configuration options appear on the basic
and advanced configuration menus.
Note:
These configuration options are repeated for each of the installed
expansion boards (A, B, C, and D).
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...