Chapter 3: Configuration and commissioning
1X-E4 Series Installation Manual
47
Input configuration
Use this menu to configure the functionality of INPUT1 and INPUT2. The default
setting for each input is included in Appendix A “Configuration presets” on page
79.
To configure an input:
1. Set the display as shown below, and then press Enter.
2. Select the input (for example, INPUT1), and then press Enter.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Remote reset.
Input activation (transition) commands reset.
Delays off
Input activation (transition) deactivates delays
(equivalent to night mode).
Input deactivation (transition) activates delays
(equivalent to day mode).
Extended fire routing delay
Input active configures extended fire routing delay.
Fire routing inhibit delay
Input active deactivates fire routing delays.
Class change
Sounders are activated while the input is active
Fault warning output open supervision
An inactive input indicates the fault warning output has
an open circuit wiring fault.