Chapter 3: Configuration and commissioning
1X-E4 Series Installation Manual
59
Advanced configuration options
The following table shows the options (available to an advanced configuration
user) for creating an advanced fire network configuration.
Table 23: Advanced configuration options for the fire network
Display
Description
Value
Firenet identifier
0 to 32
0: Stand-alone (no networking)
Default: 0
Firenet number of nodes [1]
2 to 32
Default: 2
Firenet initial zone number when
the firenet repeater type (nr) = 2n
0001 to 9999
The number has four digits. Identified by
position, these are: 1234.
Press Up to enter the first two digits of the
number (positions 1 and 2).
Press Down to enter the last two digits of the
number (positions 3 and 4).
— or —
Firenet initial panel number to be
repeated when the firenet
repeater type (nr) = Pn
01 to 32
Default: 01
Firenet global controls
On/ OFF
Default: On
Firenet loop class
A/ B
Default: B
Firenet process remote zones
On/ OFF
Default: On
Firenet repeater type
2n = Zones Repeater
Pn = Panels Repeater
Default: 2n
Firenet map
Submenu: 1 – 32
Values: On/OFF
Default: ON for nodes 1 and 2, OFF for the rest