Inaccuracy:
- Definite time (I
m
/I
set
ratio > 1.05)
±1.5 % or ±60 ms
IDMT setting parameters:
- k Time dial setting for IDMT
- A IDMT Constant
- B IDMT Constant
- C IDMT Constant
0.01…25.00, step 0.01
0…250.0000, step 0.0001
0…5.0000, step 0.0001
0…250.0000, step 0.0001
Inaccuracy:
- IDMT operating time
- IDMT minimum operating time
±2.0 % or ±30 ms
±20 ms
Retardation time (overshoot)
<5 ms
Instant operation time
Start time and instant operation time (trip):
- I
m
/I
set
ratio > 1.05
<70 ms
Reset
Reset ratio
97 % of the pick-up setting
Reset time setting
Inaccuracy: Reset time
0.010…10.000 s, step 0.005 s
±1.5 % or ±60 ms
Instant reset time and start-up reset
<55 ms
9.2.1.6 Harmonic overcurrent protection (Ih>; 50H/51H/68H)
Table. 9.2.1.6 - 314. Technical data for the harmonic overcurrent function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Residual current channel I
01
(Coarse)
Residual current channel I
02
(Fine)
Pick-up
Harmonic selection
2
nd
, 3
rd
, 4
th
, 5
th
, 6
th
7
th
, 9
th
, 11
th
, 13
th
, 15
th
, 17
th
or 19
th
Used magnitude
Harmonic per unit (× I
N
)
Harmonic relative (Ih/IL)
Pick-up setting
0.05…2.00 × I
N
, setting step 0.01 × I
N
(× I
N
)
5.00…200.00 %, setting step 0.01 % (Ih/IL)
Inaccuracy:
- Starting × I
N
- Starting × Ih/IL
<0.03 × I
N
(2
nd
, 3
rd
, 5
th
)
<0.03 × I
N
tolerance to Ih (2
nd
, 3
rd
, 5
th
)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio >1.05)
±1.0 % or ±35 ms
IDMT setting parameters:
k Time dial setting for IDMT
A IDMT constant
B IDMT constant
C IDMT constant
0.01…25.00, step 0.01
0…250.0000, step 0.0001
0…5.0000, step 0.0001
0…250.0000, step 0.0001
Inaccuracy:
- IDMT operating time
- IDMT minimum operating time
±1.5 % or ±20 ms
±20 ms
Instant operation time
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04