Figure. 5.3.20 - 154. Simplified function block diagram of the motor start/ locked rotor monitoring function.
A recommended setup for this function is for the I
2
t mode to be used in starting; if motor running/
locked rotor situations at times occur in some parts of the duty cycle during normal use, the locked
rotor protection must also be applied. The following five figures present a number of suggested
applications for the Ist> function for various situations. It is advised that the speed switch –if
available– is also used for the motor start monitoring, especially when the motor has a high load when
starting, thus making the start-up take very long.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
224