Name
Range Step Default
Description
Motor
stalled
0: Not
active
1:
Active
-
0: Not
active
The
Mo
Mottor stalled
or stalled signal is active when the measured current exceeds the "Max
overload current" setting (from the Motor running situation).
Missing
phase
0: Not
active
1:
Active
-
0: Not
active
The
Missing pha
Missing phase
se signal is activated when the measured current of one phase is
below the "No load current" setting, and the measured currents of two phases are
above the "Min locked rotor current" setting. This signal can be used for quickly
halting the motor's start-up if one phase is lost and the motor cannot start.
Load
Normal
0: Not
active
1:
Active
-
0: Not
active
The
LLoad normal
oad normal signal is active when the measured current is above the set "No
load current" and below the motor's nominal current (including the ambient and
service factor corrections).
Overloading
0: Not
active
1:
Active
-
0: Not
active
The
Ov
Overloading
erloading signal is active when the measured current exceeds the motor's
nominal current (including the ambient and service factor corrections) but does not
exceed the "Max overload current" setting.
High
overcurrent
0: Not
active
1:
Active
-
0: Not
active
The
Hig
High o
h ovver
ercurr
current
ent signal is active when the measured current is above the "Max
locked rotor current" setting and presents a situation where the motor cannot start
or stall. When this signal activates, it indicates a short-circuit fault and should
immediately be used to halt start-up or stalled situations.
Events and registers
The motor status monitoring function (abbreviated "MST" in event block names) generates events from
the detected motor status. The data register is available, based on the events.
Table. 5.3.19 - 157. Event codes.
Event number
Event channel
Event block name
Event code
Description
3969
62
MST1
1
Motor Stopped OFF
3970
62
MST1
2
Motor Starting ON
3971
62
MST1
3
Motor Starting OFF
3972
62
MST1
4
Motor Running ON
3973
62
MST1
5
Motor Running OFF
3974
62
MST1
6
Motor Stalled ON
3975
62
MST1
7
Motor Stalled OFF
3976
62
MST1
8
Load not symm ON
3977
62
MST1
9
Load not symm OFF
3978
62
MST1
10
Load normal ON
3979
62
MST1
11
Load normal OFF
3980
62
MST1
12
Overload ON
3981
62
MST1
13
Overload OFF
3982
62
MST1
14
High Overcurrent ON
3983
62
MST1
15
High Overcurrent OFF