Name
Range
Step
Default
Prot.funcs.
Description
Min
locked
rotor
current
0.1…40.0xI
n
0.1xI
n
3.5xI
n
- motor status
monitoring
- machine
thermal
overload
protection
(TM>; 49M)
- motor start/
locked rotor
monitoring
(Ist>; 48/14)
- mechanical
jam protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting
defines the current limit for when this current is exceeded
while the automatic curve selection and the control only
short time constant (stall) are in use.
Min
locked
rotor
current
A
0.1...5000.0A 0.1A
-
- motor status
monitoring
- machine
thermal
overload
protection
(TM>; 49M)
- motor start/
locked rotor
monitoring
(Ist>; 48/14)
- mechanical
jam protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting
defines the current limit for when this current is exceeded
while the automatic curve selection and the control only
short time constant (stall) are in use.
Max
locked
rotor
current
0.1…40.0xI
n
0.1xI
n
7.5xI
n
- motor status
monitoring
- machine
thermal
overload
protection
(TM>; 49M)
- motor start/
locked rotor
monitoring
(Ist>; 48/14)
- mechanical
jam protection
(Im>; 51M)
The maximum locked rotor current of the motor. This
setting defines the current limit which is maximum current
for the motor to draw in locked rotor situation (starting or
stalled). If the measured current exceeds this setting limit it
is considered to be overcurrent fault and corresponding
measures can be applied to disconnect the feeder and
motor from the supply.
Max
locked
rotor
current
A
0.1...5000.0A 0.1A
-
- motor status
monitoring
- machine
thermal
overload
protection
(TM>; 49M)
- motor start/
locked rotor
monitoring
(Ist>; 48/14)
- mechanical
jam protection
(Im>; 51M)
The maximum locked rotor current in amperes.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
279