![Arcteq AQ-M215 Instruction Manual Download Page 207](http://html1.mh-extra.com/html/arcteq/aq-m215/aq-m215_instruction-manual_2964943207.webp)
Table. 5.3.16 - 143. Event codes.
Event number
Event channel
Event block name
Event code
Description
6400
100
OPW1
0
Start ON
6401
100
OPW1
1
Start OFF
6402
100
OPW1
2
Trip ON
6403
100
OPW1
3
Trip OFF
6404
100
OPW1
4
Block ON
6405
100
OPW1
5
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, TRIP or BLOCKED. The table below
presents the structure of the function's register content.
Table. 5.3.16 - 144. Register content.
Date and time
Event code
Trigger
power
Fault power
Pre-fault
power
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
6400-6405 Descr.
Start
average
power
Trip -20ms
averages
Start -200ms
averages
0 ms...1800s
Setting groups
1...8 active
5.3.17 Underpower protection (P<; 32U)
The underpower function is used for instant and time-delayed active underpower protection. This
function is used to detect loss of load conditions when there is no significant loss of current.
Figure. 5.3.17 - 144. Operating characteristics of underpower protection.
The outputs of the function are the START, TRIP and BLOCKED signals. The underpower function
uses a total of eight (8) separate setting groups which can be selected from one common source.
The function can operate on instant or time-delayed mode.
The operational logic consists of the following:
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
206