The variables the user can set are binary signals from the system. The blocking signal needs to reach
the device minimum of 5 ms before the set operating delay has passed in order for the blocking to
activate in time.
Operating time characteristics for trip and reset
This function supports definite time delay (DT) and inverse definite minimum time delay (IDMT). For
detailed information on these delay types please refer to the chapter "General properties of a protection
function" and its section "Operating time characteristics for trip and reset".
Events and registers
The directional overcurrent function (abbreviated "DEF" in event block names) generates events and
registers from the status changes in START, TRIP and BLOCKED. The user can select which event
messages are stored in the main event buffer: ON, OFF, or both. The function offers four (4)
independent stages; the events are segregated for each stage operation.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.5 - 74. Event codes.
Event number
Event channel
Event block name
Event code
Description
5184
81
DEF1
0
Start ON
5185
81
DEF1
1
Start OFF
5186
81
DEF1
2
Trip ON
5187
81
DEF1
3
Trip OFF
5188
81
DEF1
4
Block ON
5189
81
DEF1
5
Block OFF
5190
81
DEF1
6
I0Cosfi Start ON
5191
81
DEF1
7
I0Cosfi Start OFF
5192
81
DEF1
8
I0Sinfi Start ON
5193
81
DEF1
9
I0Sinfi Start OFF
5194
81
DEF1
10
I0Cosfi Trip ON
5195
81
DEF1
11
I0Cosfi Trip OFF
5196
81
DEF1
12
I0Sinfi Trip ON
5197
81
DEF1
13
I0Sinfi Trip OFF
5248
82
DEF2
0
Start ON
5249
82
DEF2
1
Start OFF
5250
82
DEF2
2
Trip ON
5251
82
DEF2
3
Trip OFF
5252
82
DEF2
4
Block ON
5253
82
DEF2
5
Block OFF
5254
82
DEF2
6
I0Cosfi Start ON
5255
82
DEF2
7
I0Cosfi Start OF
5256
82
DEF2
8
I0Sinfi Start ON
5257
82
DEF2
9
I0Sinfi Start OFF
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
125