Name (number
of stages)
IEC
ANSI
Description
VUB (4)
U1/U2>/<
U1/U2>>/<<
U1/U2>>>/<<<
U1/U2>>>>/<<<<
47/27P/59PN
Sequence voltage protection
HOC (4)
Ih>
Ih>>
Ih>>>
Ih>>>>
50H/51H/68H
Harmonic overcurrent protection
CBFP (1)
CBFP
50BF/52BF
Circuit breaker failure protection
REF (1)
I0d>
87N
Low-impedance or high-impedance restricted earth fault/
cable end differential protection
MST
-
-
Motor status monitoring
TOLM (1)
TM>
49M
Machine thermal overload protection
LCR (1)
Ist>
48/14
Motor startup/locked rotor monitoring
FSP (1)
N>
66
Frequent start protection
NUC (1)
I<
37
Non-directional undercurrent protection
MJP (1)
Im>
51M
Mechanical jam protection
UPF (1)
PF<
55
Power factor protection
RTD (1)
-
-
Resistance temperature detectors
OPW (1)
P>
32O
Overpower protection
UPW (1)
P<
32U
Underpower protection
RPW (1)
Pr
32R
Reverse power protection
VMEM (1)
-
-
Voltage memory
PGS (1)
PGx>/<
99
Programmable stage
ARC (1)
IArc>/I0Arc>
50Arc/50NArc
Arc fault protection (optional)
Table. 5.1 - 5. Control functions of AQ-M215.
Name
IEC
ANSI
Description
SGS
-
-
Setting group selection
OBJ
-
-
Object control and monitoring
(5 objects available)
CIN
-
-
Indicator object monitoring
(5 indicators available)
PCS
-
-
Programmable control switch
mA output
-
-
Milliampere output control
Table. 5.1 - 6. Monitoring functions of AQ-M215.
Name
IEC
ANSI
Description
CTS
-
-
Current transformer supervision
VTS
-
60
Voltage tranformer supervision
DR
-
-
Disturbance recorder
CBW
-
-
Circuit breaker wear monitor
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
52