8.13 Milliampere (mA) I/O module (optional)
Figure. 8.13 - 262. Milliampere (mA) I/O module connections.
Connector
Description
Pin 1
mA OUT 1 + connector (0…24 mA)
Pin 2
mA OUT 1 – connector (0…24 mA)
Pin 3
mA OUT 2 + connector (0…24 mA)
Pin 4
mA OUT 2 – connector (0…24 mA)
Pin 5
mA OUT 3 + connector (0…24 mA)
Pin 6
mA OUT 3 – connector (0…24 mA)
Pin 7
mA OUT 4 + connector (0…24 mA)
Pin 8
mA OUT 4 – connector (0…24 mA)
Pin 9
mA IN 1 + connector (0…33 mA)
Pin 10
mA IN 1 – connector (0…33 mA)
The milliampere (mA) I/O module is an add-on module with four (4) mA outputs and one (1) mA input.
Both the outputs and the input are in two galvanically isolated groups, with one pin for the positive (+)
connector and one pin for the negative (–) connector.
This module can be ordered directly to be installed into the device in the factory, or it can be upgraded
in the field after the device's original installation when required.
The user sets the mA I/O with the mA outputs control function. This can be done at
Control
→
Device
I/O
→
mA outputs in the relay configuration settings.
8.14 Dimensions and installation
The device can be installed either to a standard 19” rack or to a switchgear panel with cutouts. The
desired installation type is defined in the order code. When installing to a rack, the device takes a
quarter (¼) of the rack's width, meaning that a total of four devices can be installed to the same rack
next to one another.