Name
Range
Step Default
Protection
functions
Description
Min
locked
rotor
current
0.1…40.0xI
n
0.1xI
n
3.5xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting
defines the current limit for when this current is exceeded
while the automatic curve selection and the control only short
time constant (stall) are in use.
Min
locked
rotor
current
A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting
defines the current limit for when this current is exceeded
while the automatic curve selection and the control only short
time constant (stall) are in use.
Max
locked
rotor
current
0.1…40.0xI
n
0.1xI
n
7.5xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
Maximum locked rotor current of the motor. This setting
defines the current limit which is maximum current for the
motor to draw in locked rotor situation (starting or stalled). If
the measured current exceeds this setting limit it is
considered to be overcurrent fault and corresponding
measures can be applied to disconnect the feeder and motor
from the supply.
Max
locked
rotor
current
A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
The maximum locked rotor current in amperes.