Table. 5.2.3 - 41. Three-phase energy calculations.
Name
Range
Step
Description
Exported Active Energy (P) (kWh
or MWh)
-999 999 995
904.00…999 999 995
904.00
0.01
The total amount of exported active energy.
Imported Active Energy (P) (kWh or
MWh)
-999 999 995
904.00…999 999 995
904.00
0.01
The total amount of imported active energy.
Active Energy (P) Export/Import
balance (kWh or MWh)
-999 999 995
904.00…999 999 995
904.00
0.01
The sum of imported and exported active energy.
Exported (Q) while Export (P)
(kVarh or MVarh)
-999 999 995
904.00…999 999 995
904.00
0.01
The total amount of exported reactive energy while
active power is exported.
Imported (Q) while Export
(P). (kVarh or MVarh)
-999 999 995
904.00…999 999 995
904.00
0.01
Total amount of imported reactive energy while
active energy is exported.
Reactive energy (Q) balance while
export (P) (kVarh or MVarh)
-999 999 995
904.00…999 999 995
904.00
0.01
The sum of imported and exported reactive
capacitive energy while active power is exported.
Exported (Q) while Import (P)
(kVarh or MVarh)
-999 999 995
904.00…999 999 995
904.00
0.01
The total amount of exported reactive energy while
active energy is imported.
Imported (Q) while Import (P)
(kVarh or MVarh)
-999 999 995
904.00…999 999 995
904.00
0.01
The total amount of imported reactive energy while
active energy is imported.
Reactive energy (Q) balance while
Import (P) (kVarh or MVarh)
-999 999 995
904.00…999 999 995
904.00
0.01
The sum of imported and exported reactive energy
while active energy is imported.
Apparent Energy (S) while Export
(P) (kVAh or MVAh)
-999 999 995
904.00…999 999 995
904.00
0.01
The total amount of exported apparent energy while
active energy is exported.
Apparent Energy (S) while Import
(P) (kVAh or MVAh)
-999 999 995
904.00…999 999 995
904.00
0.01
The total amount of exported apparent energy while
active energy is imported.
Table. 5.2.3 - 42. Single-phase energy calculations (L1...L3).
Name
Range
Step
Description
Export Active Energy Lx (kWh or MWh)
-1x10
9
…1x10
9
0.01
The exported active energy of the phase.
Import Active Energy (kWh or MWh)
-1x10
9
…1x10
9
0.01
The imported active energy of the phase.
Active Energy (P) Export/Import
balance (kWh or MWh)
-1x10
9
…1x10
9
0.01
The sum of the phase's imported and exported active
energy.
Exported (Q) while Export (P) Lx (kVarh
or MVarh)
-1x10
9
…1x10
9
0.01
The exported reactive energy of the phase while active
energy is exported.
Imported (Q) while Export (P) Lx (kVarh
or MVarh)
-1x10
9
…1x10
9
0.01
The imported reactive energy of the phase while active
energy is exported.
Reactive Energy (Q) balance while
Export (P) Lx (kVarh or MVarh)
-1x10
9
…1x10
9
0.01
The sum of the phase's imported and exported
reactive energy while active energy is exported.
Exported (Q) while Import (P) Lx (kVarh
or MVarh)
-1x10
9
…1x10
9
0.01
The exported reactive energy of the phase while active
energy is imported.
Imported (Q) while Import (P) Lx (kVarh
or MVarh)
-1x10
9
…1x10
9
0.01
The imported reactive energy of the phase while active
energy is imported.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
81