Name
Range
Step Default Prot.funcs.
Description
Safe stall
time hot
0.1…600.0s
0.1s
15.0s
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
- Machine
thermal
overload
protection
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The safe stall time when the motor is hot. This setting value is
used for the hot thermal stall curve selection in automatic
control. This parameter is also used in the motor start-up and
the number of starts calculations.
Table. 5.3.23 - 175. Pick-up settings.
Name
Description
Range
Step
Default
I
set
Pick-up setting
0.10…40.00xI
n
0.10xI
n
6.00xI
n
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Operating time characteristics for trip and reset
This function supports definite time delay (DT). For detailed information on this delay type please refer
to the chapter "General properties of a protection function" and its section "Operating time
characteristics for trip and reset".
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.23 - 176. Information displayed by the function.
Name
Range
Step
Description
Im>
condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays status of the protection function.
Expected
operating
time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs. When IDMT mode
is used, the expected operating time depends on the measured highest phase
current value. If the measured current changes during a fault, the expected
operating time changes accordingly.
Time
remaining
to trip
-1800.000...1800.000s 0.005s When the function has detected a fault and counts down time towards a trip,
this displays how much time is left before tripping occurs.
I
meas
/I
set
at the
moment
0.00...1250.00
0.01
The ratio between the highest measured phase current and the pick-up value.