Definite time function operating time setting
0.00…150.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 0.95)
±1.0 % or ±30 ms
Instant operation time
Start time and instant operation time (trip):
- I
M
/I
SET
ratio <0.95
<50 ms
Reset
Reset ratio
103 % of the pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.010…150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
9.2.1.21 Mechanical jam protection (Im>; 51M)
Table. 9.2.1.21 - 329. Technical data for the mechanical jam function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
RMS phase currents
Pick-up
Pick-up current setting
0.10…40.00 × I
N
, setting step 0.10 × I
N
Inaccuracy:
- Current
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 0.95)
±1.0 % or ±30 ms
Instant operation time
Start time and instant operation time (trip):
- I
M
/I
SET
ratio 1.05
→
<50 ms
Reset
Reset ratio
97 % of the pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.010…150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
No
Notte!
e!
• Mechanical jam protection requires that the motor running condition has been met before
tripping is possible.
9.2.1.22 Resistance temperature detectors
Table. 9.2.1.22 - 330. Technical data of the resistance temperature detectors.
Inputs
Resistance input magnitudes
Measured temperatures measured by RTD sensors
Alarm channels
12 individual alarm channels
A
AQ
Q-M215
-M215