Name
Range
Step
Default
Protection
functions
Description
Safe stall time
hot
0.1…600.0s
0.1s
15.0s
- Motor status
monitoring
- Frequent
start
protection
(N>; 48)
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The safe stall time when the motor is hot. This setting
value is used for the hot thermal stall curve selection in
automatic control. This parameter is also used in the
motor start-up and the number of starts calculations.
Starts when
cold
1…100
1
3
- Motor status
monitoring
- Frequent
start
protection
(N>; 48)
The number of allowed starts per x hours for a cold
motor.
Starts when
hot
1…100
1
2
- Motor status
monitoring
- Frequent
start
protection
(N>; 48)
The number of allowed starts per x hours for a hot
motor.
Starts in hours 1…100h
1h
1h
- Motor status
monitoring
- Frequent
start
protection
(N>; 48)
The number of hours when the parameters of the
number of allowed starts (hot and cold) apply.
Min time
between starts 0.1…600.0s
0.1s
20.0s
- Motor status
monitoring
- Frequent
start
protection
(N>; 48)
The minimum time between starts or start attempts.
Table. 5.3.19 - 156. Output signals of the motor status monitoring function.
Name
Range Step Default
Description
Motor
stopped
0: Not
active
1:
Active
-
0: Not
active
The
Mo
Mottor st
or stopped
opped signal is active when the function detects a current below the
set value of "No load current". This signal presents a situation when a motor is not
running.
Motor
starting
0: Not
active
1:
Active
-
0: Not
active
The
Mo
Mottor star
or starting
ting signal is active when a motor start-up is detected. In DOL
mode, the signal is active when the measured current exceeds the "Start detect
current" (from the Motor stopped situation); the signal deactivates when the current
decreases below the "Max overloading current".
Motor
running
0: Not
active
1:
Active
-
0: Not
active
The
Mo
Mottor running
or running signal is active when the measured current is above the set "No
load current" (as long as the Motor starting situation has passed). This signal is
released when the measured current is below the "No load current" setting.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
221