Name
Range
Step Default
Protection
functions
Description
Motor In
A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
- Undercurrent
(I<; 37)
-
Mechanical jam
protection
(Im>; 51M)
The motor's nominal current in amperes.
Nominal
starting
current
0.1…40.0xI
n
0.1xI
n
6.0xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
The motor's locked rotor current with the nominal voltage.
This setting is used for automatic curve selection and
calculation. Also, the nominal starting capacity calculation is
based on this value.
Nominal
starting
current
A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
The motor's locked rotor current in amperes.
Start
detect
current
0.1…40.0xI
n
0.1xI
n
1.5xI
n
- Motor status
monitoring
- Motor start
monitoring
(Ist>; 48/14)
The motor starting current detection limit. When in DOL or
Star-Delta mode, this setting defines the motor starting
moment when the measured current exceeds both the no-
load current limit and the start detect current limit within a
ten-millisecond period. If the current increases slower, it is
not defined as a motor start.
Start
detect
current
A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Motor start
monitoring
(Ist>; 48/14)
The motor's starting current detection limit in amperes.